Pumping Stations
Pumping stations Biocent Sp. z o.o. are complete fixtures used in gravitational and pressure sewage systems. They are used for pumping urban waste water either with or without feces, or rainwater or technological water pumping.
Each time all the parameters are adapted to the customer's particular needs, project and the building site conditions. Wide range of components allows us to tailor to all requirements while our planning department is able to choose and design any pumping station.
All fixtures are produced according to the current relulations, and we are one of the few on the market who provide liability insurance valued 2 000 000 PLN.




Built
Designation Key
Tanks
Our pumping stations are built from tanks with all technical requirements and admissions. The materials that are used for the production of tanks:- concrete type at least C35/45 (B) Diameter 800-3000mm,
- reinforced concrete (BZ) ) Diameter 800-3000mm,
- polymer concrete (PB) Diameter 1000-3000mm, Height up to 10m,
- polyethylene (PE) Diameter 600-2500mm, Height up to 6m,
- polyester (GRP) Diameter 600-2500mm, Height up to 6m,
Inlet and outfall connectors are individually arranged.


Piping
Rising mains are made of acid resistant steel. Flange connectors. Optionally a stop valve DN 50mm and a fire-fighting applicator are mounted to be able to rinse the installation. Smaller pumping stations have piping made of high-pressure.

Fittings

Pumps
Pump type: BT10


Pump type | kW | Impeller type | Pressure flange | Current consumption (A) | Q=capability | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Single-phase 230V | Three-phase 400V | Single-phase | Three-phase | l/min | 0 | 40 | 80 | 120 | 160 | 170 | |||
m3/h | 0 | 2,4 | 4,8 | 7,2 | 9,6 | 10,2 | |||||||
H=rising height (m) | |||||||||||||
BT10M | BT10T | 0,25 | channel | 1”1/4 | 2,2 | 1,1 | - | 9,0 | 8,3 | 6,3 | 4,5 | 2,4 | 1,8 |
BT10MV | BT10TV | 0,2 | Vortex | 2,0 | 1,0 | 6,5 | 5,6 | 4,8 | 3,5 | 2,0 | 1,5 |
Pumps type: BT20-50


Pump type | kW | Impeller type | Pressure flange | Current consumption (A) | Q=capability | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Single-phase 230V | Three-phase 400V | Single-phase | Three-phase | l/min | 20 | 80 | 120 | 170 | 260 | 280 | 330 | 360 | |||
m3/h | 1,2 | 4,8 | 7,2 | 10,2 | 15,6 | 16,8 | 19,8 | 21,6 | |||||||
H=rising height (m) | |||||||||||||||
BT20M | BT20 | 0,5 | channel | 1”1/4 | 4,4 | 2,0 | - | 12,2 | 9,8 | 8,3 | 6,3 | 2,9 | - | - | - |
BT30M | BT30 | 0,75 | 4,6 | 2,4 | 13,6 | 11,1 | 9,5 | 7,6 | 4 | 3,2 | - | - | |||
BT40M | BT40 | 1,1 | 7,3 | 3,0 | 17,4 | 15 | 13,4 | 11,3 | 7,5 | 6,7 | 4,6 | - | |||
- | BT5 | 1,5 | - | 3,3 | 18,4 | 16,1 | 14,5 | 12,5 | 9 | 8 | 6 | 5 |
Pump type: RG75-100


Pump type | kW | Impeller type | Pressure flange |
Current consumption (A) | Q=capability | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Single-phase 230V | Three-phase 400V | Single-phase | Three-phase | l/min | 40 | 80 | 100 | 120 | 160 | 200 | 160 | 200 | |||
m3/h | 2,4 | 4,8 | 6 | 7,2 | 9,6 | 12 | 9,6 | 12 | |||||||
H=rising height (m) | |||||||||||||||
RG75M | RG75 | 0,55 | channel | 1”1/2 | 4,8 | 2,1 | - | 7,8 | 6,8 | 6,3 | 5,7 | 4,7 | 3,4 | 2 | - |
RG100M | RG100 | 0,77 | 5,7 | 2,6 | 9,5 | 8,6 | 8,1 | 7,6 | 6,6 | 5,4 | 4,2 | 2 |
Pump type: PW-B 75-300


Pump type | kW | Impeller type | Pressure flange | Current consumption (A) | Q=capability | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Single-phase 230V | Three-phase 400V | Single-phase | Three-phase | l/min | 100 | 200 | 300 | 400 | 500 | 600 | 700 | 800 | 900 | |||
m3/h | 6 | 12 | 18 | 24 | 30 | 36 | 42 | 48 | 54 | |||||||
H=rising height (m) | ||||||||||||||||
PW-B75 | PW-B75 | 0,55 | channel | 2” | 3,9 | 1,5 | - | 8 | 6,3 | 4,8 | 3,4 | 2,2 | - | - | - | - |
PW-B100M | PW-B100 | 0,75 | channel | 5,9 | 2,1 | 10,6 | 8,7 | 7,1 | 5,5 | 4 | 2,6 | - | - | - | ||
PW-B150M | PW-B150 | 1,1 | channel | 7,3 | 2,8 | 13,1 | 11,3 | 9,5 | 7,7 | 5,9 | 4,2 | 2,4 | - | - | ||
- | PW-B200 | 1,5 | channel | - | 3,6 | 16,6 | 15 | 13,3 | 11,4 | 9,5 | 7,5 | 5,4 | 3,3 | 5 | ||
- | PW-B300 | 2,2 | channel | - | 5 | 20 | 18,3 | 16,6 | 15,1 | 13,3 | 11,3 | 9,3 | 7,2 | - | ||
PW-B75MV | PW-B75V | 0,55 | Vortex | 3,9 | 1,4 | 6,3 | 5 | 3,5 | 1,6 | - | - | - | - | - | ||
PW-B100MV | PW-B100V | 0,75 | Vortex | 5,8 | 2,1 | 7,9 | 6,7 | 5,3 | 3,7 | 1,9 | - | - | - | - | ||
PW-B150MV | PW-B150V | 1,1 | Vortex | 7,3 | 2,8 | 10,2 | 9 | 7,6 | 6,1 | 4,1 | 2,1 | - | - | - | ||
- | PW-B200V | 1,5 | Vortex | - | 3,3 | 12,5 | 11,2 | 9,8 | 8,6 | 6,4 | 4,2 | 1,6 | - | - | ||
- | PW-B300V | 2,2 | Vortex | - | 4,4 | 15,7 | 14,7 | 13,9 | 12,6 | 10,7 | 8,4 | 6,1 | 3,6 | - |
If you haven't found the pump for your pumping station, please contact our office and we will provide you with any necessary advice.
Control Cabinet

1 pump - BSP1
- Controlling and conservation of a 1-pump system
- Power supply 230V/400V
- Pump power: 0,25- 4 KW
- Alarming the user about the high level
- Outside or inside installation, IP65
- Working temperature -200C to +400C
- Start-up: direct
- Height: 390 mm
- Width: 320 mm
- Depth: 155 mm
- Measuring with floats

2 pumps - BSP2
- Controlling and conservation of a 2-pump system
- Power supply 230V/400V
- Pump power: 0,25- 4 KW
- Alarming the user about the high level
- Inside installation, IP50
- Working temperature -50C to +400C
- Start-up: direct
- Height: 385 mm
- Width: 305 mm
- Depth: 160 mm
- Measuring with floats

2 pumps - BSP3
- Controlling and conservation of a 2-pump system
- Power supply 230V/400V
- Pump power: 0,25- 4 KW
- Alarming the user about the high level
- Inside or outside installation, IP54
- Start-up: direct
- Height: 239 mm
- Width: 289 mm
- Depth: 107 mm
- Measuring with floats

2 and more pumps - BSP4
- Control cabinet based on PLC controller with the option informing and monitoring GSM (model BSP4GSM) or GPRS (model BSP4GPRS)
- Power supply 230V/400V
- Pump power: 1,5- 11 KW
- Inside or outside installation, IP66
- Start-up: direct to 5,5 kW. Over 5,5 kW
- Immersion heater with a thermostat
- Power service outlet 230V
- Measuring with floats or hydrostatic level sensor
If you haven't found the control cabinet for your pumping station, please contact us.
Manhole
We offer both passable and nonpassable manholes. Passable manholes are produced from spheroidal graphite cast iron, class D400, either round or rectangular. Nonpassable manholes are produced from stainless steel and are fitted with easy access to pumps. We provide an option of steel manhole with insulation.


Additional equipment
Access Platform
According to the regulations every pumping station which is over 6,00m high must be equipped with an access platform for the operational support. Our platforms are made of acid resistant steel. These are tilting constructions allowing unrestrained pump dismantling.
Ladder
Just like the rest of the elements, the ladder is made from acid resistant steel (stainless steel) to prevent corrosion.

Screenings Basket
Pumps in some venues are endangered with having contact with contaminations which cannot be pumped. This results in pumps' breakdowns and clogging of discharge pipes. We are meeting the needs of our clients and therefore we offer screenings baskets mounted at the inflow of the pumping station. Baskets are in guides simplifying the emptying. All construction is made of acid resistant steel.
Pumping stations for detached houses and small venues

Hallamarks
- Pumping sanitary waste water and rainwater
- Tank material: Polythene
- Maximum performance: 900 l/min
- Maximum rising height: 20m
- One or two-pump system
- Free-standing installation (optionally a base plate and guides)
- Rising pipe material PVC-U
- Diameter and height of the inlet are set individually

Pumping station type | Tank | Tank diameter [m] | Tank height [m] | Pump type | Piping diameter dn [mm] | Control cabinet type |
---|---|---|---|---|---|---|
Biopomp1D | PE | 0,6 | 1,0 | BT10M | 50 | BST1 |
Biopomp1D | PE | 0,6 | 1,8 | BT40 | 50 | BST1 |
Biopomp1S | PE | 0,8 | 1,8 | PW-B75MV | 50 | BST1 |
Biopomp2D | PE | 0,8 | 2,5 | BT50 | 50 | BST2 |
Biopomp2D | PE | 0,8 | 3,0 | RG100M | 50 | BST2 |
Biopomp2S | PE | 0,8 | 4,0 | PW-B100V | 50 | BST3 |
Biopomp2S | PE | 1,0 | 3,0 | PW-B150MV | 50 | BST3 |
If you haven't found the pumping station for you, please contact us.
Pumping stations for buildings and sewarage and rainwater sewarage systems

Hallmarks
- Pumping sanitary waste water and rainwater
- Tank material: concrete, reinforced concrete, polymer concrete, polythene, polyester
- One, two-, three-, or four-pump systems
- Pumps mounted on base plates with pipe guides made from acid resistant steel
- Rising pipe material PVC-U or acid resistant steel
- Diameter and height of the inlet are set individually
Options
- Access Platform
- Screenings Basket
- Fire-fighter hose coupling for recurrent rinsing of the rising pipe
- Control cabinet with a monitoring system GSM/GPRS


Pumping station type | Tank | Tank diameter [m] | Tank height[m] | Pump type | Piping diameter dn [mm] | Control cabinet type |
---|---|---|---|---|---|---|
Biopomp2S | PE | 1,0 | 3,0 | PW-B75V | 50 | BST3 |
Biopomp2S | GPR | 1,2 | 3,0 | PW-B100V | 50 | BST3 |
Biopomp2S | PB | 1,2 | 4,0 | PW-B100V | 50 | BST3 |
Biopomp2S | ZB | 1,5 | 4,5 | PW-B150V | 50 | BST3 |
Biopomp2D | PE | 1,5 | 4,0 | RG100M | 50 | BST3 |
Biopomp2D | ZB | 1,5 | 5,0 | PW-B200 | 63 | BST4 |
Biopomp2D | ZB | 2,0 | PW-B300 | PW-B300 | 63 | BST4 |
If you haven't found the pumping station for you, please contact us.
Underfloor and free-standing pumping stations

- Pumping sanitary waste water and rainwater, it can fitted in rooms or under the floor
- Tank material: Polypropylene
- Maximum performance: 900 l/min
- Maximum rising height: 20m
- One or two-pump system
- Free-standing installation (optionally a base plate and guides)
- Rising pipe material PVC-U
- Diameter and height of the inlet are set individually
- Optionally tiling or cobbling
Pumping station type | Tank | Tank diameter [m] | Tank height[m] | Pump type | Piping diameter dn [mm] | Control cabinet type |
---|---|---|---|---|---|---|
Biopomp1D | PE | 0,6 | 0,7 | BT10M | 50 | - |
Biopomp1S | PE | 0,8 | 1,0 | PW-B75MV | 50 | - |
Biopomp1S | PE | 0,8 | 1,0 | PW-B150MV | 50 | BST1 |
Biopomp2D | PE | 0,8 | 1,0 | PW-B200V | 50 | BST2 |


If you haven't found the pumping station for you, please contact us.